ACTUADOR DE ESTANCIAS:
* SALIDA BINARIA 4C: 4C X ON/OF, 2C X PERSIANAS, 2 X ON/OFF + 1C. PERS,
* SALIDA ELECTRÓNICA 2C. PARA ELECTROVÁLVULAS

P.V.P.:   Identifíquese para ver precios
G.D. Futurasmus:
  DESCRIPCIÓN
The room actuator is used to control electrical loads of three different building systems that are typically used in a residential, office or hotel room:The first four relay outputs of the room actuator can be set in the ETS software configuration either to blinds operation or alternatively to switching operation; mixed operation of these two modes of operation is also possible on the device. In blinds operation the relay contacts of the room actuator can be used to control electrically driven blinds, shutters, awnings, venting louvers or similar curtains for 230 V AC mains voltage. Alternatively, the actuator can switch electrical loads such as lighting systems in switching operation. The relay contacts are bistable, which means that the last switching state set remains unchanged even in the event of a mains voltage failure.

Furthermore, the room actuator has two additional electronic switching outputs, which allow si-lent control of electrothermal valve drives for heating or cooling systems. Up to 4 electrothermal valve drives can be connected to each of these electronic outputs, which are protected against overload and short-circuit.

By combining the functions of the room actuator´s outputs, in many cases it is possible to plan and execute electrical installations on a room-specific basis.

The functionalities that can be preset with the ETS independently for each output channel in blinds operation include, for instance, separately parameterizable travelling times, enlarged feedback functions, assignment to up to 5 different safety functions, an extensive sun protection function, and incorporation into scenes or forced-position applications. Centralized control of all blind outputs is also possible.

In switching operation the functionalities for each output include, for example, extensive time functions, logic operations, scenes, disabling functions or alternatively forced positions, expan-ded feedback telegrams, cyclical monitoring of the incoming telegrams and an operating hours counter. Here, too central switching of all switching outputs is possible.

Each of the electronic switching outputs has the following scope of functions: conversion of con-stant command value telegrams into a pulse-width modulated output signal (PWM). This provides quasi-constant activation of the the connected valve drives. Alternatively, conversion of switching command values. Status messaging for valve position and cyclical monitoring of the command value telegrams. Emergency operation in the event of bus voltage failure or bus and mains voltage return and forced position via bus telegram in summer and winter mode. Alarm message in case of short-circuit or overload of the switching output and anti-sticking protection for the valves. Valve drives that are closed or open when deenergized can be connected.

What is more, the room actuator monitors the mains voltage and makes it possible to transmit an alarm message to the bus in the event of a fault. The status messages "all valves closed" and "largest command value" can be transmitted to the bus in common for the two electronic switching outputs for further processing or displaying the information on other bus devices.

The controls (4 pushbuttons) on the front panel of the device permit switching the relays and also the electronic switching outputs on and off by hand even without bus voltage or in a non-programmed state. This feature permits fast checking of connected loads for proper functioning.

ETS3.0d is recommended for configuration and commissioning of the device. The advantages with regard to downloading (shorter loading times) and parameter programming are available only if this new ETS patch version or later versions are used. For ETS2 and older versions of ETS3, a separate product database is available.

The room actuator has its own mains voltage connection that is independent of the connected drives or loads. For activation of the outputs the 230 V mains voltage must always be switched on. The device electronics (BCU with application program) are supplied with power from the bus or from the mains. The device is designed for being mounted on DIN rails in closed compact boxes or in power distributions in fixed installations in dry rooms.


CATÁLOGOS ESPECIALES KNX
Estética Pulsadores 360º
Pulsadores
Smart Metering
Catálogo MDT 2017
Simulador Iddero Verso

APRENDE
Webinars gratuitos
Tutoriales uBrick
Video Tutoriales CBSE


PARTICIPA
Trivial µBrick
Trucos y consejos KNX
PRUEBA
Test gratutito visualización CBSE

ÚLTIMAS NOTICIAS KNX
Todas las noticias

ÚLTIMAS OFERTAS KNX
Todas las ofertas
DESCARGAS
KNX - Todas las marcas

FUTURASMUS KNX GROUP
Contacto
Dónde estamos
Futurasmus en el mundo
SÍGUENOS
YouTube Channel
Facebook
LinkedIN
Google+
Twitter

CENTRO DE FORMACIÓN KNX++
Futurasmus Zentrum

KNX TEST LAB CERTIFICADO
Futurasmus KNX Lab
MAYORISTA KNX ESPECIALIZADO CENTRO DE FORMACIÓN CERTIFICADO KNX
Futurasmus KNX Group es un mayorista KNX altamente especializado y activo a nivel internacional, siendo nuestro punto fuerte el excelente soporte técnico que ofrecemos. Puede visitar nuestro catálogo online en esta web, y si es un profesional del sector, pedir presupuesto sin compromiso para sus proyectos KNX. Si está interesado en comprar componentes KNX, le invitamos a leer nuestras Condiciones Generales de Venta y ponerse en contacto con nuestros agentes comerciales y técnicos por teléfono, e-mail o chat on-line. Desde 2003 somos Centro de Formación Certificado KNX++, que significa que estamos autorizados para impartir el Curso Básico KNX así como el Curso Avanzado KNX y el Curso de Tutor KNX. Somos independientes de fabricantes y también ofrecemos otros seminarios KNX especializados y monográficos. Tras haber formado a más de 1.500 KNX Partners, nuestros KNX Trainers tienen una amplia y positiva experiencia. Por favor, contacte con nosotros para cursos KNX personalizados (grupos de al menos 8 personas) en cualquier lugar del mundo (español, inglés y alemán).
USO DE COOKIES

Una cookie o galleta informática es un pequeño archivo de información que se guarda en su navegador cada vez que visita nuestra página web.

La utilidad de las cookies es guardar el historial de su actividad en nuestra página web, de manera que, cuando la visite nuevamente, ésta pueda identificarle y configurar el contenido de la misma en base a sus hábitos de navegación, identidad y preferencias.

Las cookies pueden ser aceptadas, rechazadas, bloqueadas y borradas, según desee. Ello podrá hacerlo mediante las opciones disponibles en la presente ventana o a través de la configuración de su navegador, según el caso.

En caso de que rechace las cookies no podremos asegurarle el correcto funcionamiento de las distintas funcionalidades de nuestra página web.

Más información en el apartado “POLÍTICA DE COOKIES” de nuestra página web.